综自变电站常见故障浅析
卢海平 王冶 2011-12-08
摘要:断路器作为输变电设备的主要开关设备,它的正常运行与否关系着整个电网的安全稳定可靠运行。近年来,随着科技的发展,输变电站设备自动化水平越来越高。对断路器的运行维护和检修人员也提出了更高的技术水平要求。本文作者通过总结历年来的工作经验,结合工作中遇到的实际案例,举一反三对断路器可能出现的故障和故障原因,判断方法和解决措施进行了详细说明。 关键字:综合自动化;变电站;断路器;故障 Abstract: the circuit breaker as the main switch equipment transformation equipment, its normal operation or not relates to the whole of the safe and stable and reliable operation of the power grid. In recent years, with the development of science and technology, automation level transformation station equipment is getting higher and higher. The operation and maintenance of circuit breaker repair and maintenance personnel also put forward higher technical level requirements. The author summarizes the work experience, combining over real cases work across to breaker may appear, acquire the faults and fault reasons, judging methods and measures for a detailed explanation. Key word: integrated automation substation breaker failure 随着科技的进步、社会的发展,电网结构更加坚强合理,变电站综合自动化水平越来越高,对于出现故障后如何沉着果断应对,才能迅速控制故障范围,消除故障的根源,使变电站电气设备安全、可靠、经济运行呢,我现针对综自变电站断路器常见问题进行以下简要分析: 1 断路器合闸失灵分析 断路器合闸失灵,是常出现的事故之一,值班人员若处理不当,往往拖延送电时间。因此。应迅速根据操作过程中的异常现象。初步判断故障范围和原因,进行必要的故障排除,及时恢复对用电的供电。 1.1 断路器合闸失灵的原因 1.1.1 远方或就地控制开关与操作方式不对应; 1.1.2 储能(合闸)电源空气开关在分闸位置或接触不良,合闸电源回路不通; 1.1.3 控制电源开关在分闸位置或接触不良,控制回路不通;(控故障) 1.1.4 合闸操作回路元件(辅助开关接触不良或未接通);(控故障) 1.1.5 合闸线圈损坏;(控故障) 1.1.6 断路器本体内部卡滞; 1.1.7 弹簧机构未储能或储能不到位;(控故障) 1.1.8 机械部分卡滞; 1.2 一般处理步骤 1.2.1 首先,合闸失灵后,发现断路器没有合上,应立即断开控制电源,防止合闸线圈损坏; 1.2.2 判明是否属操作不当; 1.2.3 检查合闸电源、控制电源是否正常,直流电压是否正常范围以内,弹簧储能情况,红、绿灯指示情况,人为调整后合闸送电; 1.2.4 以上情况正常,根据合闸铁芯动作与否,判明故障范围(电气回路和机械回路); 1.2.5 对于能短时间内自行查明并处理的故障,采取相应的措施处理,立即合闸送电; 1.2.6 对于不能处理的问题应查明故障类型,及时汇报上级及调度,由检修人员进行处理。 2 断路器跳闸失灵的处理 断路器跳闸失灵,在发生事故时会造成母线失压(越级跳闸)使事故扩大,甚至系统瓦解,并且由于依靠上一级电源的后备保护动作跳闸,即扩大了事故范围又延长了切除故障的时间,严重破坏了系统的稳定性,加大了设备的损坏程度。
断路器跳闸失灵分以下几种情况: 2.1 运行中的断路器发生事故保护拒动或保护动作,但断路器拒跳:(后果) 2.1.1 越级跳闸; 2.1.2 扩大事故范围; 2.1.3 延长了切除故障时间; 2.1.4 破坏系统稳定性; 2.1.5 加大了设备损坏程度。